System specification
1. Freestyle frame structure
2. Built-in microprocessor, fully intelligent
3. Redundant power module design
4. RS485 (Modbus RTU) interface
5. Easy to expand, install and maintain
6. Multiple redundancy and anti-interference technology
application | Steam turbines, water turbines, generator sets, gearboxes, compressors, water pumps, fans and other rotating machinery and equipment. | |||||||||||
overview | The system can provide continuous and on-line monitoring functions, is suitable for the application of rotating machinery, and fully meets the requirements of enterprise standards for this type of system. The system adopts the form of traditional frame structure, which is flexible and convenient. It has a variety of performance and functions that other systems do not have. The system adopts modular design and includes: VMS8010 chassis frame [required]; VMS8020 requires one or two power supplies (power supply redundancy, which can meet power supply expansion requirements) [optional redundancy]; One communication module of VMS8030 is required [optional]; One or more functional modules of VMS80XX [required]; The above components are described in detail below and in the corresponding data sheet for each system component. | |||||||||||
VMS8010 system framework | ||||||||||||
Dimensions | See Schedule 1 | |||||||||||
Hole Size | See Schedule 1 | |||||||||||
installation method | Disc | |||||||||||
VMS8020 power module | ||||||||||||
input power | (1) 90~264VAC/47~63Hz; (2) 120~370VDC | |||||||||||
power | ≤50W | |||||||||||
show | Green OK light is on | |||||||||||
describe | Provide power for the entire system and modules | |||||||||||
VMS8030 communication module | ||||||||||||
communication method | RS485 | |||||||||||
Protocol | MODBUS RTU | |||||||||||
LED display | (1) "OK" communication module is normal; (2) "TX/RX" communication module communicates with the monitoring module in the chassis frame normally | |||||||||||
VMS8090 expansion module (optional) | ||||||||||||
type | Power expansion, channel expansion | |||||||||||
Product number | VMS8110 Shaft Vibration Module | VMS8130 Swing module | VMS8120 Bearing Vibration Module | VMS8121 Bearing Vibration Module | VMS8122 Bearing Vibration Module | |||||||
show | LED display | |||||||||||
input signal type | Eddy current sensor | Eddy current sensor | Magnetic speed sensor | Piezoelectric Accelerometer | piezoelectric speed sensor | |||||||
Measurement parameters | Amplitude (pp) | Amplitude (pp), Intensity (Trms) | ||||||||||
input channel | single channel | |||||||||||
precision | ±1%FS@25℃ | |||||||||||
input resistance | >100KΩ | |||||||||||
Frequency Range | 2-500Hz±3dB | 0.5~100Hz | 10~300Hz | 10~1000Hz | 10~1000Hz | |||||||
Measuring range | Amplitude (1~500μm user defined), intensity (1~50.0mm/s user defined) | |||||||||||
Sensor power supply | -24Vdc isolation | -24Vdc isolation | No power supply (voltage input) | 4.0mA±10%, +24Vdc isolation | 4.0mA±10%, +24Vdc isolation | |||||||
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ | |||||||||||
relay | 6A/30Vdc, 6A/250Vac, SPDT dry junction | |||||||||||
Synchronization signal output | The original signal of the sensor, the output impedance is 100Ω, the maximum transmission distance is 300 meters, and it has two interfaces: BNC socket and backplane terminal | |||||||||||
Alarm level | Level 2 alarm | |||||||||||
time delay | 0~250s, with an interval of 1s | |||||||||||
alarm value | Custom | |||||||||||
alarm logic | ≥ | |||||||||||
danger bypass | enable, disable | |||||||||||
Product number | VMS8210 speed module | VMS8220 reverse speed module | VMS8230 key phase module | |||||||||
show | LED display | |||||||||||
input signal type | Eddy current sensor, speed sensor | Eddy current sensor, speed sensor | Eddy current sensor | |||||||||
Measurement parameters | revolution/minute (rpm) | |||||||||||
input channel | single channel | |||||||||||
precision | ±1%FS@25℃ | |||||||||||
input resistance | >100KΩ | |||||||||||
Measuring range | 1~9999rpm user defined | |||||||||||
Sensor power supply | -24Vdc isolation, +12Vdc isolation, no power supply | -24Vdc isolation, +12Vdc isolation | -24Vdc isolation | |||||||||
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ | |||||||||||
relay | 6A/30Vdc, 6A/250Vac, SPDT dry junction | |||||||||||
Synchronization signal output | TTL level, 0~12Vdc, output impedance 500Ω, maximum transmission distance 300 meters, with two interfaces of BNC socket and backplane terminal | |||||||||||
Alarm level | Level 2 alarm | Level 1 alarm (forward and reverse alarm) | none | |||||||||
time delay | 0~250s, with an interval of 1s | 0~250s, with an interval of 1s | ||||||||||
alarm value | Custom | |||||||||||
alarm logic | ≥ | |||||||||||
danger bypass | enable, disable | |||||||||||
Product number | VMS8310 axial displacement module | VMS8320 differential expansion module | ||||||||||
show | LED display | |||||||||||
input signal type | φ8mm eddy current sensor; φ11mm eddy current sensor | φ11mm eddy current sensor; φ25mm eddy current sensor | ||||||||||
Measurement parameters | axial displacement | |||||||||||
input channel | single channel | |||||||||||
precision | ≤1%FS@25℃ | |||||||||||
input resistance | >100KΩ | |||||||||||
Measuring range | User defined according to selected sensor | |||||||||||
Sensor power supply | -24Vdc isolation | |||||||||||
4~20mA current | Large load 750Ω, ±0.1%FS@25℃ | |||||||||||
relay | 6A/30Vdc, 6A/250Vac, SPDT dry junction | |||||||||||
Buffered signal output | Output impedance 550Ω, with two interfaces of BNC socket and backplane terminal | |||||||||||
Alarm level | Level 2 alarm | |||||||||||
time delay | 0~250s, with an interval of 1s | |||||||||||
alarm value | Custom | |||||||||||
alarm logic | ≥ | |||||||||||
danger bypass | enable, disable | |||||||||||
environment | ||||||||||||
operating temperature | -30℃~+65℃ | |||||||||||
stored temperature | -40℃~+85℃ | |||||||||||
humidity | ≤90%, non-condensing | |||||||||||
ordering information | ||||||||||||
Schedule 1 | ||||||||||||
framework epitope | Number of monitoring modules | Dimensions (mm) length x height x depth | Hole size (mm) l×h | |||||||||
5 digits | 2 | 258×161.5×200 | 227×140 | |||||||||
6 digits | 3 | 298×161.5×200 | 267×140 | |||||||||
7 digits | 4 | 338×161.5×200 | 307×140 | |||||||||
8 bits | 5 | 378×161.5×200 | 347×140 | |||||||||
9 bits | 6 | 418×161.5×200 | 387×140 | |||||||||
10 digits | 7 | 458×161.5×200 | 427×140 | |||||||||
11 bits | 8 | 498×161.5×200 | 467×140 | |||||||||
12 bits | 9 | 538×161.5×200 | 507×140 | |||||||||
13 bits | 10 | 578×161.5×200 | 547×140 | |||||||||
14 bits | 11 | 618×161.5×200 | 587×140 | |||||||||
15 digits | 12 | 658×161.5×200 | 627×140 | |||||||||
Remark: Framework epitopes = 3 fixed epitopes on the left + number of monitoring modules. (1) In the VMS8000 status monitoring system, the card slot on the left is the power module; the two card slots on the left are redundant power modules, and the redundant power module is optional. If redundant power is not configured, this card slot is reserved Power supply expansion channel; the three card slots on the left are communication modules, and the communication module is also an option. If no communication module is configured, the card slot is a reserved communication expansion channel. The card slot starting with the 4th digit is the function module card slot. (2) For the VMS8000 condition monitoring system, the number of chassis bits = 3 + the number of monitoring modules. | ||||||||||||
system module | ||||||||||||
order number | Function module name | describe | ||||||||||
VMS8010 | system framework | required | ||||||||||
VMS8020 | power module | Can be configured redundantly | ||||||||||
VMS8030 | communication module | optional | ||||||||||
VMS8090 | extension module | optional | ||||||||||
VMS8110 | Shaft Vibration Module | Equipped with φ8mm eddy current sensor | ||||||||||
VMS8120 | Bearing Vibration Module | With magnetoelectric speed sensor | ||||||||||
VMS8121 | Bearing Vibration Module | With piezoelectric acceleration sensor | ||||||||||
VMS8122 | Bearing Vibration Module | With piezoelectric speed sensor | ||||||||||
VMS8130 | Swing module | Equipped with φ8mm eddy current sensor | ||||||||||
VMS8210 | Speed module | Distribution eddy current sensor or speed sensor | ||||||||||
VMS8220 | Inverse speed module | Distribution eddy current sensor or speed sensor | ||||||||||
VMS8230 | key phase module | Distribution eddy current sensor | ||||||||||
VMS8310 | Axial displacement module | Equipped with φ8mm eddy current sensor or φ11mm eddy current sensor | ||||||||||
VMS8 320 | Differential expansion module | Equipped with φ18mm eddy current sensor or φ25mm eddy current sensor | ||||||||||